Safe Torque Off (STO) in Low-Voltage Robot Servos: Sizing and Sourcing Guide
2026/10/28

Safe Torque Off (STO) in Low-Voltage Robot Servos: Sizing and Sourcing Guide

Specify Safe Torque Off (STO) for 24V–72V robot servo drives. Compare OSSD filtering, SS1 and brake coordination, then prepare a safety-focused engineering RFQ.

Executive Summary (TL;DR)

  • Safe Torque Off (STO) inhibits drive-generated torque without isolating the DC supply. It does not guarantee standstill or prevent motion from gravity or external forces.
  • For 24V–72V robot drives, separate the torque-inhibit function from supply isolation, pre-charge, regenerative-energy handling, and motion control power.
  • Gravity-loaded joints need a validated stopping and load-holding strategy. SS1 and Safe Brake Control (SBC) can contribute, but brake command status alone does not prove mechanical engagement.
  • Specify the safety level from the machine risk assessment. Obtain the exact drive revision's safety manual, reaction-time limits, OSSD compatibility, and evidence supporting the claimed PL or SIL.
This is an expert technical summary provided by the Custom Robot Servo engineering team for industrial custom robot servo buyers.

Safe Torque Off (STO) is a drive safety function defined in IEC 61800-5-2 that prevents the drive from supplying torque-producing energy to a motor. Robotics engineers and OEM buyers should select it as part of the complete safety function, from the initiating sensor through the controller and drive to any load-holding mechanism.

For low-voltage robot servos, three decisions matter before comparing quotes: whether uncontrolled coasting is acceptable, how the axis remains supported after torque is inhibited, and whether the safety controller's outputs are compatible with the drive's STO inputs. An ordinary CANopen/EtherCAT disable command does not establish a safety-rated STO function.

Scope and review date — 28 October 2026: This global sourcing guide covers nominal 24V–72V DC BLDC/PMSM robot drives. The EU section applies to machinery placed on the EU market. It is a supplier-screening framework, not a certified circuit design or machine safety validation. Examples below are calculations using stated assumptions, not measured factory results. Medical devices and exoskeletons may require additional sector-specific assessment beyond this guide.

Preparing an actuator or drive RFQ? Submit your voltage range, envelope, and functional safety target for an engineering review.


Integrated STO versus a DC Bus Contactor

STO can avoid cycling the main DC bus for routine safety stops while keeping separately powered logic and communications available. Whether that benefit applies depends on the drive's power architecture. Integrated STO is not universally mandatory, and contactors remain useful for functions such as supply isolation or energy management where the assessed design requires them.

Compare the functions rather than assuming one component replaces another:

  1. Torque inhibition: Use the drive's documented safety function and maximum reaction time; contactor opening time and STO reaction time are device-specific.
  2. Inrush management: Reclosing a bus supply may recharge drive capacitors. Size the pre-charge circuit from capacitance, voltage, and source impedance rather than a generic current estimate.
  3. Isolation and stored energy: STO leaves the DC link energized. Provide a suitable isolation and discharge procedure for servicing.
  4. Regeneration: A rotating permanent magnet motor can return energy to the bus. Check battery charge acceptance, bus overvoltage limits, and braking hardware independently of STO.
Battery / DC supply --> isolation & pre-charge --> drive inverter --> motor
Safety controller  --> assessed STO channels  --> torque inhibition
Brake control      --> load-holding mechanism --> gravity-load support

These are separate functions; the machine risk assessment determines their coordination.

For motor architecture selection, see our comparison of BLDC versus PMSM for custom robot servos.


Hardware Circuit Architecture: Dual-Channel Independent Shutdown

A dual-channel implementation is a common approach to fault tolerance. Channel count alone does not establish Category 3/4, PL d/e, or SIL 2/3: diagnostics, common-cause failures, component data, fault exclusions, and the complete safety function also matter. ISO 13849-1:2023 describes the design and integration methodology; it does not assign a universal required PL to every robot axis.

The diagram illustrates two possible shutdown mechanisms. It is not a manufacturing schematic or evidence of certification. Each safety channel must achieve the claimed torque inhibition under the faults and conditions covered by the assessed design.

Illustrative STO Signal Paths — Not a Certified CircuitSafety Controller(Safety PLC / E-Stop)OSSD1 (+24V)OSSD2 (+24V)EDM ReadbackStatus ContactIsolation boundary: design-specificRC Filter &Schmitt TriggerOSSD Pulse FilterRC Filter &Schmitt TriggerOSSD Pulse FilterOpto / IsoChannel 1Opto / IsoChannel 2PATH 1: Gate Bias CutSolid-State P-MOS SwitchCuts +12V/+15V Upper BiasPATH 2: Logic ClampHardware Gate Pull-downClamps PWM inputs to 0V3-Phase InverterPower MOSFET BridgePhase U (MOSFETs)Phase V (MOSFETs)Phase W (MOSFETs)EDM Mirror & Discrepancy LogicFeedback meaning must match the safety manual

Shutdown paths and diagnostic feedback

One possible path removes gate-driver bias power; another inhibits gate-enable or PWM logic independently of ordinary motion-control software. Stored bias charge, driver undervoltage behavior, output-stage faults, and unintended current paths must be considered. A high-side supply switch plus a logic clamp is not automatically a safe or certified architecture.

Request the safety manual's wiring and fault-response description instead of prescribing this diagram as a required implementation. If an EDM or status output is provided, establish its polarity, diagnostic coverage, and whether it is itself safety-rated. A status bit or contact is not proof of zero torque, zero speed, or a mechanically engaged brake.


OSSD Test Pulses: Compatibility and Reaction-Time Budget

Some safety controllers and sensors use OSSD (Output Signal Switching Device) outputs with brief low-going test pulses to detect wiring faults. A drive may interpret an unsupported pulse as a shutdown request. Check pulse width, repetition interval, output type, cable capacitance, and the drive's documented input behavior together.

Illustrative RC filter calculation

A first-order RC model can explain the timing trade-off; it is not a component selection or safety approval. Assume a capacitor initially at 24 V, an ideal step to 0 V, an 11 V falling threshold, and a 1.0 ms diagnostic pulse:

V(t) = 24 × exp(-t / RC)
To remain above 11 V at 1.0 ms:
RC > 1.0 ms / ln(24 / 11) ≈ 1.28 ms

If RC = 1.5 ms:
threshold-crossing delay = 1.5 × ln(24 / 11) ≈ 1.17 ms

The strict inequality matters: equality leaves no margin. The real circuit must account for supply and threshold tolerances, temperature, component aging, repeated pulses, and incomplete recharge. This simplified calculation excludes isolation and shutdown delays. Do not add filtering to an approved safety input unless permitted by its safety manual; additional filtering can delay a genuine stop request or mask diagnostics.

Budget the maximum sensor, controller, communications, input-filter, and drive response times, then add mechanical stopping and brake engagement behavior. A faster gate-driver pin does not establish the complete STO reaction time or the machine stopping time.

Channel discrepancy monitoring

Use the manufacturer's permitted channel skew and reset sequence. For a discrepancy fault, record both channels at the drive terminals and compare pulse patterns, wiring, and connector behavior. Do not extend the discrepancy window or bypass a channel to clear an unexplained fault. Whether one channel initiates shutdown and how restart is inhibited must follow the assessed design.


Stop Category 0 (STO) vs. Stop Category 1 (SS1): The Gravity Drop Hazard

One of the most dangerous misconceptions among junior robotics integrators is treating STO as a universal emergency stop.

IEC 60204-1 stop categories describe machine stopping behavior. Drive functions can contribute to that behavior, but do not establish the complete emergency-stop function by themselves.

Stop categoryBehaviorRelevant drive functionSelection boundary
0Uncontrolled stop by removal of actuator powerSTO can implement torque inhibitionCoasting or gravity-driven motion may remain; validate the resulting hazard.
1Controlled stop, then removal of actuator powerSS1 followed by STOA time-based implementation can trigger STO after its configured delay without proving standstill; check the documented variant.
2Controlled stop with actuator power retainedSS2 leading to SOS is one safety-function arrangementRetained power and standstill monitoring need assessment; this is not an emergency-stop category.

The following timing illustration shows the coordination principle, not measured times or a guaranteed stopping profile.

Emergency Stop Dynamics: Stop Category 0 (STO) vs. Stop Category 1 (SS1 + SBC)t0 (E-Stop Trigger)Brake engagement (example)Coordinated transitionMotor Velocity (ω)Active Torque (τ)Brake State & Axis DropCat 0: Illustrative coasting profileCat 1 (SS1): Controlled Braking RampCat 0: Torque inhibited after drive responseSS1: Controlled deceleration before STOCRITICAL HAZARD ZONELoad unsupported; motion possibleBrake engagesVALIDATE TRANSITIONBrake holding verified; then STO

Worked example: a gravity-loaded joint

Consider a simplified single joint starting from rest, with a 10 kg point payload at a horizontal radius of 1.2 m. The payload alone contributes 14.4 kg·m² of inertia. Assume total output-side inertia of 20 kg·m², including the payload and reflected mechanism inertia, and a 50 ms unsupported interval measured from loss of holding torque.

Gravity torque = m × g × L = 10 × 9.81 × 1.2 = 117.72 N·m
Payload inertia = m × L² = 10 × 1.2² = 14.4 kg·m²
Initial angular acceleration ≈ 117.72 / 20 = 5.886 rad/s²
Angular displacement ≈ 0.5 × 5.886 × 0.050² = 0.00736 rad
Payload drop ≈ 1.2 × sin(0.00736) = 0.00883 m ≈ 8.8 mm

This small-angle screening example ignores friction, compliance, coupled-axis motion, initial velocity, changing geometry, and distributed arm gravity torque. It cannot predict an actual robot's drop or approve a brake. Its sourcing implication is specific: request the output-side inertia model and worst-case unsupported interval, rather than assuming the STO reaction time equals the load-holding time. With the same assumptions, doubling the unsupported interval approximately quadruples the drop.

Sourcing decision: SS1, SBC, and the holding brake

For a gravity-loaded axis, request a validated sequence covering controlled deceleration, brake engagement, torque removal, and restart. SS1 provides a stop followed by STO; SBC safely controls the brake output. SBC does not by itself prove that a mechanical brake develops sufficient holding torque.

Ask for brake holding torque, wear limits, engagement time under the specified coil suppression circuit, and the method used to verify holding capability. A holding brake may not be rated for repeated dynamic stops. Check behavior under loss of supply and safety faults, when active deceleration may be unavailable. A redundant brake or another load-support measure may be necessary depending on the risk assessment.

Review our technical analysis of mechanical holding mechanisms in the robot joint reducer and backlash guide.


Safety Architecture Comparison Matrix

Use this matrix to decide what evidence belongs in the RFQ. No row assigns an automatic PL/SIL, universal response time, or cost premium; those depend on the exact implementation and validated application.

OptionFunction in the systemResponse evidence to requestGravity-loaded axis boundaryWiring and sourcing trade-off
DC supply contactor arrangementRemoves supply power as designedOpening time, DC interruption rating, feedback and stored-energy behaviorDoes not itself hold the loadCan retain a role alongside STO; assess pre-charge and logic power separately.
Hardwired STOInhibits drive-generated torqueMaximum STO response, wiring, single-channel fault responseDoes not stop gravity motionCheck input common/reference, channel count and diagnostic wiring in the manual.
STO with SBCAdds safety-related brake-output controlSTO/SBC timing, brake ratings and holding-capability validationBrake output status does not prove holdingSpecify brake coil and suppression circuit as part of the approved configuration.
Time-based SS1Requests deceleration, then STO after a safe delayDelay tolerance and worst-case stopping-time evidenceValidate brake coordination and failed decelerationAvoid a delay chosen only from nominal payload behavior.
Monitored SS1Monitors the stop behavior according to its documented variantMonitoring limits, feedback requirements and fault responseA monitoring trip can remove active torque before the load is supportedQuote any required feedback and validation work explicitly.
FSoE safety communicationTransports safety commands to supported functionsCertified endpoints, watchdog settings and end-to-end response budgetTransport alone adds no load-holding functionCan reduce discrete command wiring; local brake/sensor wiring remains.
CIP Safety / PROFIsafe communicationTransports safety commands in the selected ecosystemExact controller/drive compatibility and supported safety functionsSame brake and stop validation duties applyConfirm the exact product variant supports the protocol; ordinary Ethernet support is insufficient.

The EtherCAT Technology Group's FSoE overview explains safety communication over EtherCAT. Support for the transport must not be read as proof that a drive includes every safe-motion function.


Electrical and Timing Parameters to Obtain Before Approval

Treat these as supplier evidence requests, not universal numerical limits. Record the safety-manual revision and test conditions for each answer.

RFQ parameterSupplier must provideIntegration check
DC bus and logic supplyPermitted operating range, regeneration limits and separate logic-power behaviorUse battery minimum/maximum and charging transients, not nominal voltage alone.
STO input levelsGuaranteed on/off thresholds, input current and reference connectionCompare with the exact safety output specification; do not assume all 24 V inputs are compatible.
OSSD pulse compatibilityAccepted pulse widths, intervals and any restrictionsCheck both channels, cable capacitance and worst-case controller settings.
Maximum STO reaction timeDefined initiating event, torque-inhibit endpoint and worst-case conditionsInclude filtering and communications; separate torque inhibition from standstill.
Channel discrepancy and resetAllowed skew, fault latch and restart sequenceVerify both channels independently without bypassing diagnostics.
Diagnostic output / EDMMeaning, polarity, electrical rating and safety statusDo not infer mechanical standstill or brake engagement from status alone.
Brake controlSupported coil, clamp circuit, engagement-time limits and brake-test methodValidate the worst-case unsupported interval and load-holding capability.
Isolation and EMCRequired insulation concept, layout constraints and immunity evidenceReview installation, grounding, wiring and environment against the approved design.
Reliability and lifecycleClaimed PL/SIL, dangerous-failure data, mission time and required testsConfirm exact hardware/firmware applicability and the complete safety-function calculation.

Packaging STO in Low-Voltage Drives

An embedded robot drive must accommodate safety circuits alongside high-current switching, connectors, and thermal paths. Evaluate the actual PCB outline and installation constraints instead of assuming a generic isolation distance will fit.

Product illustration of an embedded drive board and motors; STO capability is not established by the image

Product illustration from the site asset library; it does not identify a certified STO variant or demonstrate an isolation barrier.

Isolation, layout, and switching interference

Creepage, clearance, and insulation requirements depend on working voltage, transients, pollution degree, material group, altitude, and the insulation concept. Conformal coating does not automatically justify reducing spacing. A nominal 72 V bus must not automatically be classified as SELV/PELV.

Request the approved layout constraints and EMC evidence for the exact drive configuration. Component isolation withstand voltage and common-mode transient immunity are separate properties; neither alone proves system functional safety.

Hollow-shaft harness routing

Use the safety manual's permitted cable type, length, shielding, reference connections, and separation from motor phases. Review slip-ring contacts and high-flex cable continuity as possible faults. Safety over a supported fieldbus can reduce discrete safety command wiring, but does not remove the need for power, brake, or sensor connections.

For hollow-bore packaging details, refer to the dual-encoder robot joint servo architecture guide.


When evaluating supplier quotes, procurement managers must distinguish between vague compliance marketing and legally defensible technical documentation.

Machine risk assessment
  -> define each safety function and required PLr or SIL target
  -> select compatible sensor, logic, drive and brake arrangements
  -> calculate and document the complete function's reliability
  -> validate timing, faults, stopping and load holding
  -> control hardware/firmware revisions and lifecycle tests

Do not treat a component certificate as a machine-level declaration. PL/SIL claims depend on architecture, reliability, diagnostics, systematic measures, and application conditions. Mission time and proof-test interval are different quantities; request both where applicable rather than assuming a universal 20-year proof test. An EDM output alone does not establish a diagnostic-coverage percentage.

EU market scope and the 2027 transition

Regulation (EU) 2023/1230 generally applies from 20 January 2027, with some provisions applying earlier. Articles 51–54 address repeal, transition, and application. Products placed on the market under the Machinery Directive before the relevant date have transitional provisions; this is not a blanket recertification deadline for every existing robot.

For procurement, identify the applicable conformity-assessment route and document the safety-related software/configuration controls. Do not assume a signed-firmware feature or a third-party STO certificate alone establishes CE conformity. Manufacturer obligations following a modification depend on whether it meets the Regulation's definition of a substantial modification; changing a wire is not automatically that determination. These EU duties do not replace destination-specific requirements elsewhere.

For budgeting certification, prototype testing, and tooling expenses, read our breakdown of hidden costs in custom robot servo manufacturing.


Engineering & Procurement Checklist: What to Specify in an STO RFQ

Use this checklist to make safety assumptions and supplier deliverables explicit before quote approval:

  • 1. Safety function and target: State the hazard, initiating event, safe state, required PLr/SIL target, and machine boundary from the risk assessment.
  • 2. Exact configuration: Record drive model, hardware and firmware revisions, supported safety functions, permitted wiring, and change-control obligations.
  • 3. Power and input interface: Specify bus limits and the exact controller output; obtain STO thresholds, input current, references, and cable restrictions.
  • 4. OSSD compatibility: Match documented pulse widths and repetition intervals without adding unapproved filtering.
  • 5. Timing budget: Obtain maximum drive response and add upstream delays, stopping behavior, and brake engagement for the complete function.
  • 6. Diagnostics and restart: Define channel fault response, discrepancy behavior, feedback meaning, reset and unexpected-restart prevention.
  • 7. Gravity support: Specify holding torque, engagement delay, loss-of-power behavior, brake-test method and any redundant support required.
  • 8. Safety evidence: Obtain the safety manual, applicable certificates/assessment reports, reliability data, mission time, and required proof/periodic tests. Resolve scope gaps before approval.
  • 9. Installation and EMC: Review the approved insulation, grounding, shielding, thermal limits, vibration and cable constraints in the actual joint envelope.
  • 10. Acceptance and lifecycle: Agree unit-level production checks, application validation, traceable records, periodic tests, and who approves safety-related changes.

Incorporate these requirements directly into your custom robot servo engineering RFQ.

Organize your procurement milestones using the custom robot servo RFQ guide.


Frequently Asked Questions (FAQ)

Does an ordinary drive-disable command count as STO?

No. A normal CiA 402 disable or zero-current command does not by itself provide a safety-rated torque-inhibit function. A certified safety architecture may include assessed safety software or a safety fieldbus; ordinary motion-control firmware is not a substitute for the documented safety function and its fault response.

Does STO protect maintenance personnel from electrical shock?

No. STO does not provide electrical isolation. The DC link and motor connections may remain hazardous, including through stored or regenerated energy. Follow the equipment's supply isolation, discharge, and verification procedure before servicing. Low nominal bus voltage does not establish a safe-to-touch condition.

What happens when STO is requested at full speed?

After the specified reaction time, the drive inhibits torque production. Inertia, gravity, or external loads may keep the mechanism moving. A spinning permanent magnet motor may feed energy into the DC link through available inverter paths; evaluate that behavior using the drive manual rather than relying on it as a controlled brake. Select and validate SS1 where controlled stopping before torque removal is needed.

How should I investigate an intermittent channel-discrepancy fault?

Capture both input channels at the drive, the fault log, controller pulse settings, cable routing, and reference voltages. Compare those records against the manual's allowed pulses and channel skew. Inspect contacts, connectors, slip rings, supply dips, and switching-noise coupling. Do not bypass a channel or widen timing limits without an approved safety review.

What documents support a claimed PL e or SIL 3 drive function?

Request the exact product/revision safety manual, the claimed function's assessment or certificate scope where available, reliability data, timing limits, installation restrictions, and lifecycle tests. An FMEDA summary or other assessment evidence may be available under confidentiality. Whether independent certification is legally required depends on the product and conformity-assessment route; not every supplier must provide a public full FMEDA or a Notified Body certificate. The machine integrator still has to validate the complete safety function.


Sources & Technical References

These official references have different scopes. The ISO catalogue describes a methodology, the EU legal text defines EU obligations, and the ETG overview explains a communication approach. None supplies universal drive input thresholds, brake times, or price premiums. Obtain the applicable standards and the exact product safety manual for design approval.

  1. ISO — ISO 13849-1:2023: Safety of machinery — Safety-related parts of control systems — Part 1: General principles for design. The official abstract describes design/integration methodology, including software; it does not prescribe the required PL for a specific robot application.
  2. European Parliament and Council — Regulation (EU) 2023/1230 on machinery: Consult the current text, Articles 3, 18, 25 and 51–54, and Annex III for definitions, modification responsibilities, assessment, transition and safety requirements. General application is 20 January 2027; some provisions apply earlier.
  3. EtherCAT Technology Group — Safety over EtherCAT (FSoE) overview: Official background on safety communication over EtherCAT. This public overview is not the complete ETG.5100 specification or a certificate for any particular servo drive.

Evidence boundary: Reviewed 28 October 2026 as a sourcing guide. The RC and gravity examples are explicitly hypothetical calculations. The product illustration and conceptual diagrams are not factory test records or certification evidence.


Partner with an Engineering OEM for Custom STO Servo Drives

Use the checklist above to prepare a custom low-voltage drive inquiry. Our team can review the mechanical envelope, electrical interface, and supplier-documentation requirements before a prototype scope is agreed. Safety capability, certification scope, and validation responsibilities must be confirmed for the exact proposed configuration.

Send your mechanical CAD envelope, DC bus voltage, continuous and peak phase current ratings, target safety level (PL d / PL e), and target production volumes. We will review your requirements and provide an engineering evaluation and DFM feedback.

Inquiry Email

[email protected]

Include drawings, torque/speed, protocol, and prototype quantity.

Instant Chat

WhatsApp Engineering Support

Direct response from our engineering team.